Category
Dam1-630 3p 250-630A Tama Adjustable Asta Approved Moulded Case Circuit Breaker MCCB
Introduction DAM1 series Thermal and magnetic adjustable range of Moulded Case Circuit Breakers are designed and manufac
Basic Info
Model NO. | DAM1-630 |
Poles Number | 3 |
Type | Circuit Breaker |
Function | Conventional Circuit Breaker, Circuit-Breaker Failure Protection, Overcurrent Protection |
Certification | ISO9001-2000, CE, CB, CCC, Asta, Semko, RoHS |
Base | BMC Unflaming Material |
Thermal Adjustable | Min:0.7-Max:1in |
Magnetic Adjustable | Min:5-Max:10in |
Rated Insulation Voltage | 1000V |
Rated Operation Voltage | 400/415V |
Outline Dimension | 255X140X103.5mm |
Transport Package | Carton |
Specification | 250, 315, 400, 500, 630A |
Trademark | CDADA, OEM, ODM |
Origin | Shanghai, China |
HS Code | 8536200000 |
Production Capacity | 10000PCS/Month |
Product Description
IntroductionDAM1 series Thermal and magnetic adjustable range of Moulded Case Circuit Breakers are designed and manufactured to world-class standards.Provide overload and short-circuit protection for all applications.The thermal&magnetic elements, adjustable over a wide band,make these MCCBs ideal for any distribution application.
Advantages
°Wide range:400A to 630A(AC)
°Compact dimensions
°Adjustable thermal setting(70-100%)In.
°Adjustable magnetic setting(5-10times)In.
°Push to trip button provision.
°Separate main and arcing contacts
°Wide range of accessories.
Thermal Adjustable Magnetic adjustable Circuit Breakers (TAMA) | ||||||
Model | DAM1-630 | |||||
Breaking Capacity Code | N | S | H | G | ||
Rated Current of Frame size- Inm (A) | 400A | |||||
Rated Current-In(40,50 or 55ºC) (A) | 250 - 315 (350)- 400 - 500 - 630A | |||||
Ui(a.c.) 50-60Hz (V) | 750V | |||||
Ue(a.c.) 50-60Hz(V) | 400/415V | |||||
Number of Pole | 3P /4P | |||||
Icu (KA) | 35 | 50 | 70 | 85 | ||
Ics (KA) | 26.25 | 37.5 | 52.5 | 52.5 | ||
Icm(peak)(KA) | 70/0.25 | 110/0.25 | 154/0.2 | 187/0.2 | ||
Uimp (V) | 8000 | |||||
Dielectric Propery (V) | 3000 | |||||
lonization distance (mm) | ≤60/0 | |||||
Endurance | Total Cycles | 5000 | ||||
Electrical Life | 1000 | |||||
Mechanical Life | 4000 | |||||
Over Current trip | Thermal adjustable | Min:0,7In -Max:1In | ||||
Magnetic adjustable | 5In-10In | |||||
Category (EN 60947-2/IEC 60947-2) | Main circuit | A/B | ||||
Auxiliary circuit | AC-15 | |||||
Under Voltage Release | √ | |||||
Shunt Release | √ | |||||
Auxiliary Contact | √ | |||||
Alarm Contact | √ | |||||
Auxiliary and Alarm Contact | √ | |||||
Handle Operation Mechanism | √ | |||||
Electrical Operastion Mechanism | √ | |||||
DIN clips | - | |||||
Terminal cover | √ | |||||
Phase seperator | √ | |||||
Extention Handle | √ | |||||
W (mm) | 3P | 140 | ||||
4P | 184 | |||||
L (mm) | 3P | 254 | ||||
4P | 254 | |||||
H (mm) | 3P | 103.5 | ||||
4P | 103.5 | |||||
Weight | Fixed version 3P/4P | 5.1/7.1 | ||||
Plug-in version 3P/4P | 6.5/8.5 | |||||
Draw out version 3P/4P | 6.5/8.7 |